Shopping security
The Allen-Bradley 1771-OBD/C, also cataloged as the 1771-OBD Digital Output Module, operates as a dedicated hardware component for controlling external devices within 1771 PLC-5 I/O System platforms.
| Parameter | Specification |
|---|---|
| Model | 1771-OBD/C |
| Brand | Allen-Bradley |
| Origin | United States |
| Module Type | Digital Output Module |
| Output Channels | 16 isolated DC outputs |
| Output Voltage Range | 10-60 VDC |
| Output Current per Channel | 2 A maximum (resistive load) |
| Pilot Duty Output | 0.2 A per output |
| Current per Module | 8 A maximum |
| Backplane Current | 400 mA at 5 VDC |
| Isolation Voltage | 1500 VAC for 1 minute |
| Power Dissipation | 7 W |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Humidity | 5 to 95% non-condensing |
| Dimensions | 178 x 50 x 180 mm |
| Weight | 0.84 kg (1.85 lbs) |
The 1771-OBD/C handles 16 independent solid-state DC load drivers to maximize local I/O density scaling inside standard 1771 universal racks. To maintain synchronous operational sequencing over Profinet or EtherNet/IP deterministic networks via an adapter module, the 1771-OBD/C restricts its internal backplane bus logic consumption to 400 mA at 5 VDC. This strict boundary optimizes the chassis power margin, allowing proper firmware flash compatibility across legacy systems and preventing bus execution dropouts during dense channel switching events.
Q: What is the total combined electrical current limit for the 1771-OBD/C module?
A: The cumulative electrical current across all 16 channels must not exceed 8 A total for the module, even though individual discrete channels can handle up to a 2 A maximum resistive load.
Q: Does the 1771-OBD/C possess internal short-circuit protection for its channels?
A: No. The internal electronic circuitry lacks embedded individual fuses. External fuse protection per output channel is necessary to guard the internal switching components against overcurrent states.
Q: Is online hot-swapping supported for this module inside an energized 1771 chassis?
A: No. The physical architecture of the 1771 rack requires isolation and complete power de-energization prior to module removal or insertion to protect against backplane logic faults and component stress.